OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05592
PWS Name: BOB BELLONI RANCH
 
Who Was Contacted and Phone: Jim Pinson (541) 269-0321
Contact Date: 05/23/2017
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
None
 
Details: SUMMARY: reference sensor light for UV unit DETAILS: Jim said they have decided to order a 2nd light sensor for the new UV unit so that they can do the required monthly monitoring of its intensity (checking the duty sensor versus a reference sensor). That will enable them to switch over to UV as their primary disinfection method, and allow them to start using the UV version of the monthly surface water treatment report rather than the chlorine one. I emailed him what hell need to record regarding the monthly sensor checks for his own internal records, where to write the % difference between the sensors on the monthly operating report, and reminded him of the 2 data slots on the UV page that are required to be filled in (the sensor check being one of them). I re-sent the UV monthly reporting form that I had previously customized for the Belloni Boys Ranch system. Jim says the UV unit has been up and running for a couple months already. ACTION NEEDED: Wait to hear when they have received the 2nd sensor and may start the monthly checks of their current light sensor versus a reference sensor.


More information for this water system: SDWIS ID 3924
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login