OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93750
PWS Name: WILLOWCREEK ELEM SD #84
 
Who Was Contacted and Phone: SAM BLACKBURN (541) 473-0207
Contact Date: 08/10/2016
Contacted By: HENRY, ROBERT (DWP)
Contact Method/Location: Office
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: CORROSION CONTROL ISSUES DETAILS: The Vale School District owns and operates the water system at Willowcreek Elementary School. The school has a groundwater system that serves approximately 80 students and staff. The school has a treatment system to remove arsenic. The system is an ion exchage resin filter. This system was installed in 2006. Ion exchange systems can often cause lead and copper corrosion issues. There is also hypochlorination for chlorine residual maintenance. The main building was constructed in 1954. The water pipe used was galvanized iron. Large portions of this pipe have been removed and replaced with PVC. The galvanized iron pipe was reported to be in very poor condition. The kindergarten building was constructed in the 1980’s. In addition to replacement of much of the old galvanized iron, the Willowcreek Elementary School has replaced fixtures in the kindergarten and 1st/2nd grade classrooms. The lead level was reduced, but the February 2016 lead level remained over the Action Level. The Circuit Rider was contacted to provide analysis of corrosion control options for the school. Finalized corrosion control analysis and recommendations. ACTION NEEDED: Provide further assistance if requested.


More information for this water system: SDWIS ID 3081
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login