OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00029
PWS Name: PERIWINKLE MOBILE HOME PARK
 
Who Was Contacted and Phone: Dave Kuntz (541) 926-0700
Contact Date: 10/10/2017
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Water Quality Issues DETAILS: Dan Vaage visited the site on 10/26/2017 to meet with Dave Kuntz, to assess the system, and find a possible solution. The system employs a Stenner 85MHP17 with a #5 tube injecting soda ash for corrosion control. Dave mixes the soda ash at 3 lbs. per 5 gallons in a 55-gallon drum. The Stenner turns on and off with the well pump and was turned up to 10. The operator has noted a history of clogging at the soda ash injection point (a tee where water coming from the well makes a 90 to go into the 200-gallon pressure tank). A pH reading was taken at first user and read 7.1. Dan returned on 11/01/2017 to test both the raw and finished water. The raw water was reading a pH of 6.8, TDS of 164 and temperature of 64.4F. The finished water read a pH of 6.9, TDS of 181 at a temperature of 62.2F.The clogging of the injection point should be addressed, either by moving the injection point or by starting a cleaning schedule or both. The Stenner pump should have a new tube installed and it should be verified that there is no possible backflow through the check valve and pump. It is also recommended that the system bump up the soda-ash mix to one pound per gallon. If the pump is verified to be dispensing an adequate amount of soda ash and this is not eliminating the lead problem, the Periwinkle MHP should look into connecting to the City of Albany’s water distribution system for water service. ACTION NEEDED: None.


More information for this water system: SDWIS ID 3220
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login