OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00613
PWS Name: PENDLETON, CITY OF
 
Who Was Contacted and Phone: Klaus Hoehna (541) 966-0249
Contact Date: 01/19/2018
Contacted By: WORD, AMY (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Level 1 triggered - multiple TC detections DETAILS: The water system collected its remaining two monthly routine coliform samples on 1/17/18. Both samples came back positive for total coliform. The samples had a free chlorine residual of 0.31 and both were taken at the same location. (Fire Station 2) There was no clear indication of where the source of the total coliform bacteria was. There was a sampling tube attached to the faucet that after the detections was taken to the Citys treatment plant lab and sanitized. Discussed the Citys options and recommended filling out the Level 1 form and trying to determine the source of contamination as opposed to taking additional compliance samples. ACTION NEEDED: Complete Level 1 form and turn in to DWS. Review coliform sampling plan and sampling procedure to see if it can be fine tuned.
 
Associated Alerts: COLI17616 - 01/18/2018 - COLIFORM, TOTAL (TCR)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 4231