OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00389
PWS Name: HUBBARD, CITY OF
 
Who Was Contacted and Phone: Michael Krebs (503) 982-9429
Contact Date: 11/09/2015
Contacted By: STEGALL, CAROLYN (MARION COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Total Coliform Positive After Positive E.coli in the Distribution DETAILS: Spoke with Mike about progress over the weekend. It appears that City Hall may be the only building in town affected, no known leaks or damage to building plumbing. They have examined the outside of the building looking for leaks and will monitor the water meter to see if there is an excessive water flow. They have raised the chlorine residual from 0.1 to 0.25. It is our recommendation they maintain 0.2 chlorine residual as their baseline. Reminded Mike to report residual on ALL water samples turned in for sampling. If samples pulled today still have TC will increase residual to 0.5 until further testing. Filters and screens were removed from the faucets used for sampling. They have a waste water treatment lab on site and will have tandum samples they can monitor and will use those samples to increase chlorine if needed. They understand those samples are not regulatory but informational only. They have the Public Notice in place and have heard from only one individual about illness. ACTION NEEDED: Boil water in effect until clean samples are obtained.
 
Associated Alerts: COLI14920 - 11/09/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3328
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login