OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00063
PWS Name: WICKIUP WATER DISTRICT
 
Who Was Contacted and Phone: Daniel Waterbury (503) 458-6555
Contact Date: 02/22/2018
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: E. Coli positive routine sample taken 2-21-18 DETAILS: I received a call from Daniel Waterbury about an E. Coli positive routine sample taken from the distribution system on 2-21-18 at a sample location marked George Hill. I let Dan know that he needed to take 3 repeat samples within 24 hours, which he did on 2-22-18. If any of the repeat samples came back positive, then that would be considered an MCL violation, a boil water notice would need to be issued, and a Level 2 Coliform Investigation would be needed. I e-mailed some information on the coliform sampling requirements and the October 2015 Pipeline article on new coliform rule requirements as well as a Tier 1 boil notice template in case the repeat samples resulted in an MCL violation. I recommended to Dan that he do some preparation to issue a public notice and that we would talk on 2-23-18 after the repeat sample results are known. Dan called back on 2-23-18 to report that the repeat samples all came back absent of coliform bacteria and he faxed the repeat results to our office. ACTION NEEDED: Operator to report E. coli detection in the CY2018 Consumer Confidence Report. No further action necessary due to the repeat samples being absent of coliform bacteria.
 
Associated Alerts: COLI17660 - 02/22/2018 - COLIFORM, E. COLI , COLIFORM, TOTAL (TCR)

COLI17660 - 02/22/2018 - COLIFORM, E. COLI , COLIFORM, TOTAL (TCR)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3875