Most Recent Water System Survey | ||||
Survey Date: | May 22, 2024 | |||
Notification Date: | May 24, 2024 (2 days) | |||
Regulating Agency: | DWS (REGION 1) | |||
Survey Frequency: | 5 YR - Visit the Water System Surveys page to see the list of surveys due each year. | |||
Deficiencies: | Outstanding Performer! No deficiencies were identified. |
Water System Site Visit History | ||||||
Reason | Visit Date | Frequency | Next Due | Notification Date (Days after survey) |
Responsible Agency |
Comments and Deficiencies |
---|---|---|---|---|---|---|
Sanitary Survey, Finished (SNSV) | 05/22/2024 | 5 YR | * | 05/24/2024 (2) | REGION 1 | Show details |
Sanitary Survey, Finished (SNSV) | 12/18/2019 | 5 YR | * | 01/28/2020 (41) | REGION 1 | Show details |
Sanitary Survey, Finished (SNSV) | 12/18/2014 | 5 YR | * | 12/31/2014 (13) | REGION 1 | Show details |
Sanitary Survey, Finished (SNSV) | 12/20/2011 | 3 YR | * | 01/17/2012 (28) | DWP | Show details |
Sanitary Survey, Finished (SNSV) | 12/09/2008 | 3 YR | * | 12/29/2008 (20) | DWP | Hide details |
Comments: Deficiencies notes are as follows: 1. Backflow Prevention Device Testing. Water District needs to contact Blue Mtn Lumber Products to verify if there is a backflow prevention device on the water line. If so, it needs to be tested annually. 2. Radiological Monitoring Not Current. Sample 1 quarter for Gross Alpha, and 2 quarters for Radium 226/228 and Uranium. 3. Lead and Copper Monitoring Not Current. Collect 5 samples during summer of 2009. 4. No approved Written Coliform Sampling Plan. 5. No ERP. 6. No O&M Manual. 7. No Certified Operator. Water system no longer has DRC at required level. 8. No Annual CCR This site visit has not been entered into the deficiency database. | ||||||
Sanitary Survey, Finished (SNSV) | 05/22/2002 | 5 YR | * | DWP | Show details | |