OHA Drinking Water Services
OR41
PWS ID: 94365 ---- OREGON HOUSE, THE

Most Recent Water System Survey
Survey date: Feb 17, 2009
Notification date: Apr 21, 2009 (63 days)
Regulating agency: DWS (REGION 2)
Survey frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Significant deficiencies and unmet rule requirements:
This site visit has not been entered into the deficiency database.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 02/17/2009 5 YR  * 04/21/2009 (63) REGION 2 Hide details
  Comments:
SOURCE - If Seagull well is reactivated as a source, they will need to make the wellhead watertight, add screen to vent, and add sample tap. FINISHED WATER - Add locks to tanks; screen all lines that connect to tanks; fix screen on vent. MONITORING - No Coliform Sampling Plan. MANAGEMENT - No Emergency Response Plan; no Operations Manual; No Plan Review on new raw water tank. REC: Add pressure relief valve close to pressure tanks; Calibrate turbidimeter quarterly; Complete shelter over wellhead.
This site visit has not been entered into the deficiency database.

Sanitary Survey, Finished (SNSV) 08/16/2000  * DWP Show details