OHA Drinking Water Services
OR41
PWS ID: 90476 ---- LITTLE RIVER CHRISTIAN CAMP

Most Recent Water System Survey
Survey Date: Oct 09, 2024
Notification Date: Nov 13, 2024 (35 days)
Regulating Agency: DWS (REGION 2)
Survey Frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Well Construction Does not meet setbacks from hazardsOct 09, 2024 Overdue
Finished Water Storage Roof and access hatch not watertightDec 30, 2024
Well Construction Sanitary seal and casing not watertightDec 30, 2024
Disinfection Minimum CT requirement not met all timesDec 30, 2024
Disinfection No means to adequately determine flow rate on contact chamber effluent lineDec 30, 2024
Disinfection Failure to calculate CT values correctlyDec 30, 2024
Disinfection No means to adequately determine disinfection contact time under peak flow and minimum storage conditionsDec 30, 2024
Surface Water Treatment Turbidity standards not metDec 30, 2024
Surface Water Treatment Turbidimeters not calibrated per manufacturer or at least quarterlyDec 30, 2024
Bold text indicates that resolving this deficiency is a top priority.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 10/09/2024 5 YR  * 11/13/2024 (35) REGION 2 Show details
Water Treatment Plant Site Visit (TRTP) 10/09/2024 6 MN 04/09/2025 11/13/2024 (35) REGION 2 No details
Sanitary Survey, Finished (SNSV) 08/29/2019 5 YR  * 12/10/2019 (103) REGION 2 Show details
Water Treatment Plant Site Visit (TRTP) 08/29/2019 6 MN 02/29/2020 12/10/2019 (103) REGION 2 No details
Water Treatment Plant Site Visit (TRTP) 08/28/2014 6 MN 02/28/2015 10/16/2014 (49) REGION 2 No details
Sanitary Survey, Finished (SNSV) 08/26/2014 5 YR  * 10/16/2014 (51) REGION 2 Show details
Sanitary Survey, Finished (SNSV) 09/03/2009 5 YR  * 09/08/2009 (5) DOUGLAS COUNTY Hide details
  Comments:
surface water treatement deficients. turbidity standards not met. no means to adequately determine flow rate on contact chamber effluent line. pH, temp, chlorine resid not measured daily at first user failure to calculate ct values correctly no means to adequately determine disinfection contact time under peak flow and minimum storage conditions no coliform sampling plan no ops and maintenance manual rg 12/15/09
This site visit has not been entered into the deficiency database.

Sanitary Survey, Finished (SNSV) 09/09/2004 5 YR  * DOUGLAS COUNTY Show details
 




More information for this water system: SDWIS ID 672
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login