Significant deficiencies and unmet rule requirements:
Category Significant deficiency or unmet rule requirement Due date Resolved date
Management & Operations Emergency response plan not completed (CWS, NTNC)Mar 01, 2021 Mar 23, 2021 - Late
Management & Operations No operations and maintenance manualApr 30, 2021 * May 24, 2021 - Late
Bold text indicates a significant deficiency. All others are unmet rule requirements.
* A corrective action plan has been submitted for this significant deficiency or unmet rule requirement.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 10/13/2020 5 YR  * 10/26/2020 (13) DEPT OF AGRICULTURE Show details
Sanitary Survey, Finished (SNSV) 08/04/2015 5 YR  * 08/28/2015 (24) DEPT OF AGRICULTURE No details
Sanitary Survey, Finished (SNSV) 11/09/2010 5 YR  * 11/23/2010 (14) DEPT OF AGRICULTURE Hide details
  Comments:
The deficiencies noted are as follows:

Finished Water Storage Deficiencies
1. No flap, valve, screen or equivalent on drain.
2. No screened vent.

Monitoring Deficiencies
1. Sampling not current.

The recommendations noted are as follows:

1. A summary of monitoring requirements was discussed. Coliform samples due quarterly, next Nitrate sample due January 2011, and
raw source water sample will need to be taken annually.
2. Please note that the critical deficiencies noted on your survey for treatment are not required to be corrected at this time since you are
choosing to treat your system. If in the future it is determined that treatment is required, you will be asked to acquire an NSF approved
UV unit and proceed through the plan review process and the bypass to the UV light that is currently in the system will need to be omitted.

Category Significant deficiency or unmet rule requirement Due date Resolved date
Finished Water Storage No flap valve, screen, or equivalent on overflow or drainNot tracked
Finished Water Storage No screened ventNot tracked
Monitoring & Reporting Monitoring not currentNot tracked
Significant deficiency and unmet rule requirement dates were not tracked prior to 1/1/2014.