OHA Drinking Water Services
OR41
PWS ID: 90808 ---- GALICE RESORT

Most Recent Water System Survey
Survey Date: Oct 21, 2021
Notification Date: Jan 05, 2022 (76 days)
Regulating Agency: DWS (REGION 2)
Survey Frequency: Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Disinfection Failure to calculate CT values correctlyMar 11, 2024 * Overdue
Finished Water Storage No flap valve, screen, or equivalent on overflowMar 31, 2022 * Apr 28, 2023 - Late
Management & Operations No operations and maintenance manualMar 31, 2022 * May 11, 2023 - Late
Management & Operations Emergency response plan not completedMar 31, 2022 * May 11, 2023 - Late
Monitoring & Reporting No coliform sampling planMar 31, 2022 * May 11, 2023 - Late
* Corrective Action Plan has been submitted for this deficiency.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 10/21/2021  * 01/05/2022 (76) REGION 2 Show details
Water Treatment Plant Site Visit (TRTP) 10/21/2021 5 YR 10/21/2026 01/05/2022 (76) DWP No details
Sanitary Survey, Finished (SNSV) 10/04/2016 5 YR  * 10/06/2016 (2) REGION 2 Show details
Sanitary Survey, Finished (SNSV) 03/24/2011 5 YR  * 04/15/2011 (22) JOSEPHINE COUNTY Show details
Water Treatment Plant Site Visit (TRTP) 03/24/2011 5 YR 03/24/2016 04/13/2011 (20) DWP Hide details
  Comments:
The deficiencies noted are as follows:

Treatment Deficiencies
1. Turbidity not measured in correct location.
2. Turbidity standards not met.
3. Turbidity profiles not conducted at least quarterly.
4. Turbidimeters not calibrated according to manufacturers specifications.
5. Tracer study or alternative not conducted.
6. No call-out alarm or auto shut-off for high turbidity.
7. Chlorine residuals are not recorded as required.
8. CT values not being calculated correctly.
9. DPD or EPA approved method of measuring chlorine residual not used.
10. Free chlorine residual not maintained.
11. Minimum CT requirement not met at all times.
12. Contact chamber does not have effluent flow meter.
13. pH, temperature, and chlorine residual not measured daily at first user.


Sanitary Survey, Finished (SNSV) 04/27/2006 5 YR  * 05/03/2006 (6) JOSEPHINE COUNTY No details
Sanitary Survey, Finished (SNSV) 08/31/2001 5 YR  * JOSEPHINE COUNTY Show details