OHA Drinking Water Services
OR41
PWS ID: 94157 ---- HAMLET QUICK-STOP

Most Recent Water System Survey
Survey Date: Feb 17, 2022
Notification Date: Mar 15, 2022 (26 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Disinfection pH, temperature, and chlorine residual not measured daily at first userMay 03, 2022 Feb 20, 2022
Disinfection Failure to calculate CT values correctlyMay 03, 2022 Feb 20, 2022
Other Treatment Non-NSF approved chemicalsMay 03, 2022 Feb 20, 2022
Surface Water Treatment Turbidity standards not metMay 03, 2022 Feb 20, 2022
Surface Water Treatment Turbidimeters not calibrated per manufacturer or at least quarterlyMay 03, 2022 Feb 20, 2022
Surface Water Treatment Incorrect location for compliance turbidity monitoringMay 03, 2022 Feb 20, 2022
Management & Operations No operations and maintenance manualMay 04, 2022 * May 04, 2022
Management & Operations Emergency response plan not completedMay 04, 2022 * May 04, 2022
Operator Certification Attend the essentials of SW treatment course.Jun 02, 2022 * Jun 02, 2022
* Corrective Action Plan has been submitted for this deficiency.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 02/17/2022 5 YR  * 03/15/2022 (26) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 02/17/2022 1 YR 02/17/2023 03/15/2022 (26) REGION 1 No details
Sanitary Survey, Finished (SNSV) 08/23/2016 5 YR  * 09/06/2016 (14) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 08/23/2016 1 YR 08/23/2017 09/06/2016 (14) REGION 1 No details
Sanitary Survey, Finished (SNSV) 07/26/2011 5 YR  * 09/02/2011 (38) DEPT OF AGRICULTURE Hide details
  Comments:
The deficiencies noted are as follows:

Treatment and Disinfection Deficiencies
1. Turbidimeters not calibrated per manufacturer’s recommendation or at least quarterly
2. The UV disinfection unit was not working at the time of the survey
3. Cartridge filter was not operating properly at the time of the survey

Monitoring Deficiencies
4. Coliform sampling not current

Management & Operations Deficiencies
5. No Operation and Maintenance Manual
6. No Emergency Response Plan

Category Deficiency Due Date Resolved Date
Management & Operations No operations and maintenance manualNot tracked
Management & Operations Emergency response plan not completedNot tracked
Monitoring & Reporting Monitoring not currentNot tracked
Other OtherNot tracked
Surface Water Treatment Turbidimeters not calibrated per manufacturer or at least quarterlyNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Sanitary Survey, Finished (SNSV) 08/01/2006 3 YR  * 09/14/2006 (44) DEPT OF AGRICULTURE No details
Water Treatment Plant Site Visit (TRTP) 08/01/2006 3 YR 08/01/2009 09/14/2006 (44) DEPT OF AGRICULTURE Show details
Sanitary Survey, Finished (SNSV) 01/08/1991 5 YR  * DWP Show details
 




More information for this water system: SDWIS ID 2198
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login