OHA Drinking Water Services
OR41
PWS ID: 00187 ---- CLACKAMAS RIVER WATER

Most Recent Water System Survey
Survey date: Aug 16, 2023
Notification date: Aug 31, 2023 (15 days)
Regulating agency: DWS (REGION 1)
Survey frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Significant deficiencies and unmet rule requirements: Outstanding Performer!
No significant deficiencies or unmet rule requirements were identified for this survey.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 08/16/2023 5 YR  * 08/31/2023 (15) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 08/16/2023 3 YR 08/16/2026 08/31/2023 (15) REGION 1 No details
Sanitary Survey, Finished (SNSV) 03/05/2020 3 YR  * 04/08/2020 (34) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 03/05/2020 1 YR 03/05/2021 04/08/2020 (34) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/22/2015 5 YR  * 12/29/2015 (68) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/22/2015 5 YR 10/22/2020 12/29/2015 (68) REGION 1 No details
Sanitary Survey, Finished (SNSV) 12/11/2012 3 YR  * 02/13/2013 (64) DWP Hide details
  Comments:

The deficiencies noted are as follows:

Finished Water Storage Deficiencies
1. There was a small hole atop hatch on Otty South reservoir.
2. Screen drain gutters on all non-shoebox hatches on reservoirs – specifically Mather, and Otty East – to prevent animal entry and nesting. Inspect regularly to prevent clogging on the small drain spout.

The following recommendations were made as well:

1. Improve resolution of quarterly filter profiles for them to become a useful metric to evaluate filter media health and resilience.
2. Consider monitoring alkalinity when using Alum, lest the pH plummet.
3. Monitor raw TOC monthly to maintain the DBP monitoring reduction. OAR 333-061-0036(4)(e)(C)

Category Significant deficiency or unmet rule requirement Due date Resolved date
Finished Water Storage Roof and access hatch not watertight or adequately securedNot tracked
Finished Water Storage No flap valve, screen, or equivalent on overflow or drainNot tracked
Significant deficiency and unmet rule requirement dates were not tracked prior to 1/1/2014.
Water Treatment Plant Site Visit (TRTP) 12/11/2012 3 YR 12/22/2015 02/13/2013 (64) DWP No details
Sanitary Survey, Finished (SNSV) 12/09/2009 3 YR  * 12/30/2009 (21) DWP Show details
Water Treatment Plant Site Visit (TRTP) 12/09/2009 3 YR 12/09/2012 12/30/2009 (21) DWP No details
Sanitary Survey, Finished (SNSV) 03/08/2007 3 YR  * 03/08/2007 (0) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 04/03/2003 3 YR  * DWP Show details