OHA Drinking Water Services
OR41
PWS ID: 00922 ---- VERNONIA, CITY OF

Most Recent Water System Survey
Survey Date: Sep 27, 2022
Notification Date: Nov 29, 2022 (63 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Surface Water Treatment Turbidimeters not calibrated per manufacturer or at least quarterlyJan 17, 2023 Jan 01, 2023
Surface Water Treatment For conventional or direct filtration: Turbidity profile not conducted on individual filters at least quarterlyJan 17, 2023 Jan 01, 2023
Management & Operations Emergency response plan not completedApr 01, 2023 * Jun 23, 2023 - Late
Management & Operations Master plan not current (≥ 300 con.)Jun 01, 2023 * Jun 23, 2023 - Late
* Corrective Action Plan has been submitted for this deficiency.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 09/27/2022 3 YR  * 11/29/2022 (63) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 09/27/2022 3 YR 09/27/2025 11/29/2022 (63) REGION 1 No details
Sanitary Survey, Finished (SNSV) 12/18/2019 3 YR  * 01/31/2020 (44) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 12/18/2019 6 MN 06/18/2020 01/31/2020 (44) REGION 1 No details
Sanitary Survey, Finished (SNSV) 04/20/2016 3 YR  * 05/06/2016 (16) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 04/20/2016 6 MN 10/20/2016 05/06/2016 (16) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/16/2013 3 YR  * 11/07/2013 (22) REGION 1 Hide details
  Comments:
The deficiencies noted are as follows:

Treatment and Disinfection Deficiencies
1. Settled water not measured daily - Corrected 12/23/13
2. Chlorine residuals are not measured and recorded as required - Corrected 12/23/13
3. pH, Temperature, and chlorine residual not measured daily at first user- Corrected 12/23/13
4. Failure to calculate CT values correctly - Corrected 12/23/13
Finished Water Storage Deficiencies
1. Hatch not locked or adequately secured - Corrected 12/23/13
2. Roof and access hatch not watertight - Corrected 12/23/13
Monitoring Deficiencies
1. Sampling not current - Corrected 12/23/13
Management & Operations Deficiencies
1. No Operation and Maintenance Manual

Category Deficiency Due Date Resolved Date
Finished Water Storage Hatch not locked or adequately securedNot tracked
Finished Water Storage Roof and access hatch not watertightNot tracked
Management & Operations No operations and maintenance manualNot tracked
Monitoring & Reporting Monitoring not currentNot tracked
Disinfection Chlorine not measured & recorded as requiredNot tracked
Disinfection pH, temperature, and chlorine residual not measured daily at first userNot tracked
Disinfection Failure to calculate CT values correctlyNot tracked
Surface Water Treatment For conventional filtration: Settled water not measured dailyNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Water Treatment Plant Site Visit (TRTP) 10/16/2013 6 MN 04/16/2014 REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 06/29/2011 6 MN 12/29/2011 07/08/2011 (9) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 10/12/2010 3 YR  * 11/09/2010 (28) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/12/2010 6 MN 04/12/2011 11/09/2010 (28) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 06/12/2007 3 YR  * 06/21/2007 (9) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/09/2002 3 YR  * DWP Show details
 




More information for this water system: SDWIS ID 3998
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login