OHA Drinking Water Services
OR41
PWS ID: 95397 ---- UPPER COLUMBIA MILL ---- INACTIVE

Most Recent Water System Survey
Survey date: Dec 11, 2013
Notification date: Dec 26, 2013 (15 days)
Regulating agency: DWS
Survey frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Significant deficiencies and unmet rule requirements:
This site visit has not been entered into the deficiency database.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 12/11/2013 5 YR  * 12/26/2013 (15) DWP Hide details
  Comments:
Deficiencies from the 2013 water system survey:
  • The seal or gasket between the well cap and casing does not appear watertight to prevent contaminants from entering.
  • No written coliform sampling plan.
  • The DCVA in the Fire Control Building connected to the potable water supply must be tested yearly by a certified backflow assembly tester.
  • No written operations and maintenance manual.
  • No written emergency response plan.

Deficiencies corrected or a corrective action plan is due by May 2, 2014.
This site visit has not been entered into the deficiency database.

Sanitary Survey, Finished (SNSV) 11/13/2008 5 YR  * 12/09/2008 (26) REGION 1 Show details