| Most Recent Water System Survey | |||||||||||||||||||||
| Survey date: | Feb 11, 2026 | ||||||||||||||||||||
| Notification date: | Feb 27, 2026 (16 days) | ||||||||||||||||||||
| Regulating agency: | DWS (REGION 1) | ||||||||||||||||||||
| Survey frequency: | 3 YR - Visit the Water System Surveys page to see the list of surveys due each year. | ||||||||||||||||||||
| Significant deficiencies and unmet rule requirements: |
Bold text indicates a significant deficiency. All others are unmet rule requirements. * A corrective action plan has been submitted for this significant deficiency or unmet rule requirement. |
||||||||||||||||||||
| Water System Site Visit History | ||||||
| Reason | Visit date | Frequency | Next due | Notification date (Days after survey) |
Responsible agency |
Comments and significant deficiencies or unmet rule requirements |
|---|---|---|---|---|---|---|
| Sanitary Survey, Finished (SNSV) | 02/11/2026 | 3 YR | * | 02/27/2026 (16) | REGION 1 | Show details |
| Sanitary Survey, Finished (SNSV) | 12/02/2021 | 5 YR | * | 04/27/2022 (146) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 12/02/2021 | 5 YR | 12/02/2026 | 04/27/2022 (146) | REGION 1 | No details |
| Sanitary Survey, Finished (SNSV) | 08/31/2016 | 5 YR | * | 09/30/2016 (30) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 08/31/2016 | 5 YR | 08/31/2021 | 09/30/2016 (30) | REGION 1 | No details |
| Sanitary Survey, Finished (SNSV) | 12/05/2013 | 5 YR | * | 02/12/2014 (69) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 12/05/2013 | 5 YR | 12/05/2018 | 02/12/2014 (69) | REGION 1 | Show details |
| Sanitary Survey, Finished (SNSV) | 09/24/2010 | 3 YR | * | 10/03/2010 (9) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 09/24/2010 | 3 YR | 09/24/2013 | 10/03/2010 (9) | REGION 1 | Show details |
| Sanitary Survey, Finished (SNSV) | 05/29/2007 | 6 MN | * | 05/29/2007 (0) | REGION 1 | Hide details |
| Comments: Deficiencies: 1. System not conducting backwash filter profiles. 2. System not measuring pH, temperature and chlorine at first user. 3. MCLs for DBPs have been exceeded every year since 2002. 4. System does not have alarms for low chlorine or high turbidity. 5. System is not sampling quarterly for DBPs. 6. Public notices are not being issued for M&R violations. 7. System does not have written protocols for under-certified operators. This site visit has not been entered into the deficiency database. | ||||||
| Sanitary Survey, Finished (SNSV) | 08/28/2003 | 3 YR | * | DWP | Show details | |