OHA Drinking Water Services
OR41
PWS ID: 00786 ---- SKYVIEW ACRES WATER COMPANY

Most Recent Water System Survey
Survey date: Oct 30, 2023
Notification date: Dec 07, 2023 (38 days)
Regulating agency: CLACKAMAS COUNTY
Survey frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Significant deficiencies and unmet rule requirements:
Category Significant deficiency or unmet rule requirement Due date Resolved date
Operator Certification No DRC at required certification level Apr 11, 2024 Mar 04, 2025 - Late
Bold text indicates a significant deficiency. All others are unmet rule requirements.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 10/30/2023 5 YR  * 12/07/2023 (38) CLACKAMAS COUNTY Show details
Sanitary Survey, Finished (SNSV) 11/17/2020 3 YR  * 12/30/2020 (43) CLACKAMAS COUNTY Show details
Sanitary Survey, Finished (SNSV) 12/07/2017 3 YR  * 02/08/2018 (63) CLACKAMAS COUNTY Show details
Sanitary Survey, Finished (SNSV) 11/25/2014 3 YR  * 01/22/2015 (58) CLACKAMAS COUNTY Show details
Sanitary Survey, Finished (SNSV) 12/29/2011 3 YR  * 01/31/2012 (33) CLACKAMAS COUNTY Show details
Sanitary Survey, Finished (SNSV) 01/30/2008 3 YR  * 12/26/2008 (331) DWP Hide details
  Comments:

The deficiencies noted are as follows:

Finished Water Storage Deficiencies
1. Assure a flap valve or equivalent is in place on reservoir overflow to prevent blocking or entry of contamination.

Distribution System Deficiencies
2. A cross-connection ordinance or other enabling authority must be developed { OAR 333-061-0070 }
3. Cross-connection records must be kept current. All backflow prevention devices must be tested annually.

Monitoring Deficiencies
4. A written coliform sampling plan must be developed See the enclosed sample plan template for additional information.

Management & Operations Deficiencies
5. An Emergency Response Plan needs to be developed Tony Fields, Security Coordinator, can answer questions: (971) 673-2269. { OAR 333-061-0064 (1) }
6. No operations and maintenance manual. Please see the enclosed information for further information. { OAR 333-061-0064 (2) }

Operator Certification Deficiencies
7. A written protocol for non-certified operators needs to be developed. { OAR 333-061-0225 (5) }
This site visit has not been entered into the deficiency database.