OHA Drinking Water Services
OR41
PWS ID: 00321 ---- GLADSTONE, CITY OF

Most Recent Water System Survey
Survey Date: Oct 20, 2022
Notification Date: Nov 03, 2022 (14 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
No deficiencies were identified.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 10/20/2022 3 YR  * 11/03/2022 (14) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 09/10/2019 3 YR  * 09/30/2019 (20) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 09/21/2016 3 YR  * 11/15/2016 (55) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 11/19/2013 3 YR  * 12/30/2013 (41) DWP Show details
Sanitary Survey, Finished (SNSV) 04/13/2010 3 YR  * 06/01/2010 (49) DWP Hide details
  Comments:

The deficiencies noted are as follows:

Finished Water Storage Deficiencies
1. Lock hatches at all three reservoirs.

Water Quality Monitoring
2. Create a coliform sampling plan. See enclosed simplified template, ...

Distribution System Deficiencies
3. Cross connection devices are not tested annually.
4. No annual summary report was submitted to this office.

Management and Operation Deficiencies
5. A written protocol for operators is required such that under-certified operators make operational decisions according to the protocol established by the operator in Direct Responsible Charge. Please see the enclosed information. { OAR 333-061-0225 (5) }
6. No operations and maintenance manual. Please see the enclosed information. { OAR 333-061-0064 (2)(c) }
7. Make your Emergency Response Plan.It should include, but is not limited to:
    a. Communications & authority
    b. Water system security
    c. Water system hazard review
    d. Emergency equipment and water supplies
    e. Emergency response procedures
8. Get major modifications approved through this Department's plan review process including all water main line extensions and replacements.
9. Submit a master plan to this office.

Category Deficiency Due Date Resolved Date
Cross Connection Annual summary report not issued (CWS)Not tracked
Cross Connection Testing records not current (CWS, NTNC, TNC)Not tracked
Finished Water Storage Hatch not locked or adequately securedNot tracked
Management & Operations No operations and maintenance manualNot tracked
Management & Operations Emergency response plan not completedNot tracked
Management & Operations Major modifications not approved (plan review)Not tracked
Management & Operations Master plan not current (≥ 300 con.)Not tracked
Monitoring & Reporting No coliform sampling planNot tracked
Operator Certification No protocol for under-certified operatorNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Sanitary Survey, Finished (SNSV) 12/06/2007 3 YR  * 07/02/2008 (209) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 08/26/2004 3 YR  * DWP Show details
 




More information for this water system: SDWIS ID 4039
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login