OHA Drinking Water Services
OR41
PWS ID: 00414 ---- JOSEPH, CITY OF

Most Recent Water System Survey
Survey Date: Jul 22, 2022
Notification Date: Aug 02, 2022 (11 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Disinfection Chlorine not measured & recorded as requiredSep 20, 2022 Jul 24, 2022
Other The bypass piping around the filters and reservoir represents a potential for untreated water to enter the distribution systemMay 01, 2023 * Apr 27, 2023
* Corrective Action Plan has been submitted for this deficiency.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 07/22/2022 3 YR  * 08/02/2022 (11) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 07/22/2022 3 YR 07/22/2025 08/02/2022 (11) REGION 1 No details
Sanitary Survey, Finished (SNSV) 11/13/2019 3 YR  * 11/20/2019 (7) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 11/13/2019 3 YR 11/13/2022 11/20/2019 (7) REGION 1 No details
Sanitary Survey, Finished (SNSV) 08/09/2016 3 YR  * 09/08/2016 (30) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 08/09/2016 3 YR 08/09/2019 09/08/2016 (30) REGION 1 No details
Sanitary Survey, Finished (SNSV) 08/21/2013 3 YR  * 12/09/2013 (110) REGION 1 Hide details
  Comments:
The deficiencies noted are as follows:

Finished Water Storage Deficiencies
1. No flap valve, screen, or equivalent on drain
Distribution Deficiencies
1. Backflow or cross-connection devices not tested annually
2. Annual summary report not submitted
3. No Cross Connection Control Specialist
Management & Operations Deficiencies
1. Annual consumer confidence report not published as required
Operator Certification Violations
1. No protocol for under certified operator

Category Deficiency Due Date Resolved Date
Cross Connection Annual summary report not issued (CWS)Not tracked
Cross Connection Testing records not current (CWS, NTNC, TNC)Not tracked
Cross Connection No cross connection control specialist (CWS ≥300 connections)Not tracked
Finished Water Storage No flap valve, screen, or equivalent on overflowNot tracked
Management & Operations Annual CCR not submitted (CWS)Not tracked
Operator Certification No protocol for under-certified operatorNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Water Treatment Plant Site Visit (TRTP) 08/21/2013 3 YR 08/21/2016 12/09/2013 (110) REGION 1 No details
Sanitary Survey, Finished (SNSV) 09/30/2009 3 YR  * 11/13/2009 (44) DWP Show details
Water Treatment Plant Site Visit (TRTP) 09/30/2009 3 YR 09/30/2012 11/13/2009 (44) DWP No details
Sanitary Survey, Finished (SNSV) 05/31/2006 3 YR  * 07/05/2006 (35) REGION 3 No details
Water Treatment Plant Site Visit (TRTP) 05/31/2006 3 YR 05/31/2009 07/05/2006 (35) REGION 3 No details
Sanitary Survey, Finished (SNSV) 01/15/2003 3 YR  * DWP Show details
 




More information for this water system: SDWIS ID 4360
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login