OHA Drinking Water Services
OR41
PWS ID: 00724 ---- ST HELENS, CITY OF

Most Recent Water System Survey
Survey Date: Jul 22, 2021
Notification Date: Oct 13, 2021 (83 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies: Outstanding Performer!
No deficiencies were identified.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Water Treatment Plant Site Visit (TRTP) 07/26/2021 5 YR 07/26/2026 10/13/2021 (79) DWP No details
Sanitary Survey, Finished (SNSV) 07/22/2021 5 YR  * 10/13/2021 (83) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 09/23/2015 5 YR  * 10/28/2015 (35) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 09/23/2015 5 YR 09/23/2020 10/28/2015 (35) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/26/2012 3 YR  * 11/16/2012 (21) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/26/2012 3 YR 10/26/2015 11/16/2012 (21) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 11/03/2011 3 YR 11/03/2014 12/02/2011 (29) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 11/24/2009 3 YR  * 01/12/2010 (49) DWP Hide details
  Comments:
Direct integrity testing of the membranes not performed daily (OAR 333-061-0032(4)(e)(B)). At the time of the survey, weekly direct integrity testing of the membranes was being performed, however, recent rule changes (Long-Term 2 Enhanced Surface Water Treatment Rule) now require this testing to be performed daily. the roof was unable to keep debris, rainwater, birds, and other contaminants out of the water. The screening around the inlet piping must be replaced with material that prevents entry of these contaminants. The photographs below illustrate the deficiencies found for the 500,000 gallon “Bowl” reservoir: Annual VOC Sampling for EP-A (Ranney Collectors) not completed (OAR 333-061-0036(3)(b)(C)(i)). In the last water system survey conducted in 2006, it was documented that annual VOC sampling was required for EP-A (Ranney Collectors), consistent with OAR 333-061-0036(3)(b)(C)(i). Our records indicated that sampling for VOC was last completed in 2005. Please resume annual VOC sampling for EP-A and submit any results for sampling that may have been completed in 2006, 2007, 2008, or 2009.
This site visit has not been entered into the deficiency database.

Water Treatment Plant Site Visit (TRTP) 11/24/2009 6 MN 05/24/2010 01/12/2010 (49) DWP Show details
Sanitary Survey, Finished (SNSV) 09/27/2006 3 YR  * 12/12/2006 (76) REGION 1 No details
Water Treatment Plant Site Visit (TRTP) 09/27/2006 3 YR 09/27/2009 12/12/2006 (76) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/15/2002 5 YR  * DWP Show details
 




More information for this water system: SDWIS ID 4242
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login