Deficiencies:
Category Deficiency Due Date Resolved Date
Finished Water Storage No flap valve, screen, or equivalent on overflowJan 18, 2021 Dec 16, 2020
Disinfection Chlorine not measured & recorded as requiredJan 18, 2021 Oct 27, 2020
Surface Water Treatment Turbidimeters not calibrated per manufacturer or at least quarterlyJan 18, 2021 Dec 16, 2020
Surface Water Treatment Incorrect location for compliance turbidity monitoringJan 18, 2021 Oct 27, 2020


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 10/26/2020 5 YR  * 11/30/2020 (35) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/26/2020 5 YR 10/26/2025 11/30/2020 (35) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/14/2015 5 YR  * 11/12/2015 (29) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/14/2015 1 YR 10/14/2016 11/12/2015 (29) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 09/23/2010 3 YR  * 10/27/2010 (34) YAMHILL COUNTY Hide details
  Comments:
The deficiencies noted are as follows:

Treatment Deficiencies
1. CT values not being calculated correctly.

The comments and recommendations are as follows:

1. Tilikum Retreat Center is required to monitor for Nitrates once per year, Coliform once per month
and to maintain and provide surface water treatment rule documents monthly.
2. I have included direction on how to perform a tracer study. Please review and become acquainted
with the process.

Category Deficiency Due Date Resolved Date
Disinfection No means to adequately determine disinfection contact time under peak flow and minimum storage conditionsNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Sanitary Survey, Finished (SNSV) 07/25/2005 5 YR  * YAMHILL COUNTY Show details
 




More information for this water system: SDWIS ID 3017
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login