OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 01062
PWS Name: RAINBOW ROCK VILLAGE MHP
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed in Distribution
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Dec 12, 2019
Date Lifted: Dec 18, 2019
 
Contacted By: PARRY, BETSY (DWP - SPRINGFIELD)
Who Was Contacted: Brenda Vasquez
Contact Phone: 541-254-1909
 
Details: On 12/11/19, Brenda learned that their routine coliform sample contained E. coli. She collected 3 repeat samples on 12/12, while investigating the problem. They determined the chlorine feed pump was not working properly because of a hole in the tube, and the situation had not yet been resolved when the 3 repeat samples were collected. They replaced the tube later on 12/12. They have also had concerns about the accuracy of their portable chlorine meter - a Hach digital meter. This week, Hach agreed to replace the unit. [Their online chlorimeter has realistic measurements (which vary over time), but the portable one has had results that seem too consistent.]

Update 12/16/2019:  The results of the repeat samples collected 12/12 were positive for coliform (total). This was expected because they had not yet identified a problem and taken corrective action when the repeats were collected. On Monday, 12/16, the chlorine level at the treatment plant was normal (they keep it at around 0.9 or 1.0 at the entry point). They collected coliform samples today and will ship them to the lab.

Lifted 12/18/2019:  System lifted the boil advisory on Wednesday, 12/18, once they received absent results for the 3 samples collected on 12/16/19. The chlorine residual level is good, and they also received a replacement Hach chlorimeter that is working well.

Associated Alerts: COLI19579 - 12/11/2019 - COLIFORM (TCR) , E. COLI  See also: 12/11/2019

COLI19593 - 12/16/2019 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4007
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login