OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 05201
PWS Name: COLD SPRINGS WATER CO
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed at GW Source Without Treatment
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Jan 15, 2021
Date Lifted: Mar 05, 2021
 
Contacted By: DAVIS, ASHLEY ( )
Who Was Contacted: Scott Peterson
Contact Phone: 971-312-7734
 
Details: Routine monthly sample had come back positive for E coli on Jan 14. Three repeats and a triggered source sample were collected this day. Source sample came back positive for E coli on Jan 15. Operator was instructed to issue a boil water notice for residents and nursery staff. He agreed to generate a written notice with provided template and call all residents to ensure they understand. 5 source samples were collected from spring on Jan 15 and submitted to lab, we await results. Hillsboro Pump will shock chlorinate system for operator and then resampling will be conducted on Jan 18.

Lifted 03/05/2021:  This system has installed 4-log chlorine disinfection and successfully went through plan review for installation with OHA. A routine sample free of E coli and total coliform was taken on Feb 24th and facility has adjusted chlorine injection system to meet appropriate residual at first user. OHA final plan review approval was issued March 5th. Facility has been instructed that they have met all requirements to lift boil water advisory. Operator was instructed to inform residents and nursery staff.

Associated Alerts: COLI20751 - 01/15/2021 - COLIFORM (TCR) , E. COLI  See also: 01/15/2021



More information for this water system: SDWIS ID 4385
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login