OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01515
PWS Name: ROW RIVER VALLEY WATER DIST
 
Who Was Contacted: Jim Eckstine
Contact Phone: 541-946-1655 (Email address hidden)
Contact Date: 09/20/2022
Contacted By: MACPHERSON, JAMES (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: Increase DBP monitoring to quarterly since Row River’s August DBP sample exceeded the MCL for HAA5s. This exceedance isn’t an MCL violation (which is long-run annual average based), though it triggers increased monitoring frequency.

The rule language follows for reference from 333-061-0036-(4)(e) Increased Monitoring:
(A) At water systems where annual or less frequent monitoring is required according to subsections (4)(c) or (4)(d) of this rule, monitoring must be increased to dual sample sets collected every 90 days at all locations if a TTHM or HAA5 sample exceeds the MCL at any location.
(B) At water systems where increased monitoring is conducted according to paragraph (4)(e)(A) of this rule, samples must be collected at the
monitoring locations specified in the monitoring plan developed according to paragraph (4)(c)(B) of this rule.
(C) Monitoring may be returned to routine if at least four consecutive quarters of increased monitoring has been conducted and the LRAA for
every monitoring location is less than or equal to 0.060 mg/L for TTHM and 0.045 mg/L for HAA5.
 
Associated Alerts: CHEM9883 - 09/09/2022 - TOTAL HALOACETIC ACIDS (HAA5)



More information for this water system: SDWIS ID 5068
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login