OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05581
PWS Name: WEISS ESTATES WATER SYSTEM
 
Who Was Contacted: Michael Murphy
Contact Phone: -- (Email address hidden)
Contact Date: 05/10/2023
Contacted By: DOWNS, KENT (DWP)
Contact Method/Location: Email
 
Assistance Type: VIOLATION RESPONSE
Reasons: SWTR
 
Details: Failure to meet CT in February and March
05.10.2023-Michael provided copy of the public notices for failure to meet CT in Feb, March and April. The Tier 2 notice for failure to submit CCT recommendations is still pending. Corinne was advised to finish collecting the 2 rounds of WQPs and work with the Circuit Rider on the corrosion control recommendations.

05.09.2023-Michael reached out reporting that the system failed to meet the required CT during the month of April. Next steps: Michael was advised to post a tier 2 notice for failure to meet CT in April. Michael has instructed operators to maintain chlorine level high in an attempt to meet CT. The pH ranges are normal, as are water temperatures. The main change is the contact time calculation which went 75 minutes (based on a theoretical calculation) to 24 minutes (based on a tracer study).

04.13.2023-Corinne reported that she has not received from Michael Murphy (DRC) a copy of the revised SWT report for March. Next steps: Corinne was advised to provide a revised version of the report and a copy of the Tier 2 notices for February and March for failing to meet CT.

04.07.2023-The SWT report for the month of March calculated achieved CT using 75 minutes of contact time. That value is incorrect. the actual contact time is 24 minutes. I emailed Corinne requesting a revised version of the SWT report using the correct contact time.

03.24.2023-I emailed Corinne requesting a copy of the Tier 2 notice for their failure to meet CT during the month of February. Michael Murphy was also Cced on the email.
 
Associated Violations: Viol #903453607, 04/01/2023 - 06/20/2023: LCR - Failure to Submit CCT Recommendation

Viol #903453608, 04/01/2023 - 04/30/2023: TCR - Routine Coliform - Did Not Report ANY

Viol #903453605, 03/01/2023 - 03/31/2023: SWTR - Failure to Meet CT

Viol #903453603, 02/01/2023 - 02/28/2023: SWTR - Failure to Maintain EP Disinfection  See also: 03/22/2023

Viol #903453604, 02/01/2023 - 02/28/2023: SWTR - Failure to Meet CT  See also: 03/22/2023

Viol #903453602, 01/01/2023 - 01/31/2023: SWTR - Failure to Meet CT  See also: 03/27/2023, 03/22/2023



More information for this water system: SDWIS ID 3923
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login