PWS ID: OR41 94398
PWS Name: ELK RIVER CAMPGROUND
 
Who Was Contacted: Miranda Wagner
Contact Phone: (Email address hidden)
Contact Date: 12/04/2025
Contacted By: DOWNS, KENT (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: TC Positive on November 10, 2025

12.04.2025-A level 2 coli investigation was triggered after RP samples collected on 11.13.25 tested TC positive. The investigation was conducted on December 4, 2025. Based on the results of the investigation it is believed that the causes of the resent multiple TC positive samples are related to the following factors:

- The system is not maintaining a detectable amount of free chlorine in the distribution system: Free chlorine concentration at the entry point and at other sites within the distribution measured at 0.0 mg/L.
- Disinfection equipment failure: The chlorine pump is experiencing failure. It is not successfully pumping sodium hypochlorite (liquid chlorine) through the discharge line and into the water storage tank.
- Failure to monitor and replace chlorine supply: The day tank was observed to have a very low level of sodium hypochlorite. The low level of chemical in the tank likely caused the chlorine pump to lose its prime, leading to a failure in disinfection.

Corrective Actions: The system is advised to perform chemical pump inspection and maintenance, perform routine free chlorine monitoring to ensure a detectable amount of free chlorine in the system, shock the system and once free chlorine levels are back to normal, the operator should collect a Special sample to ensure the TC contamination has been addressed. A copy of the L2 investigation has been submitted to DMCE.

11.12.2025-The operator was contacted and advised to follow their coliform sampling procedure. Specifically, the operator was provided with detailed instructions to collect three RP samples and one TG sample at the source. Additionally, the operator was instructed to collect the repeat samples prior to any corrective action. The operator was also advised to verify that the chlorine system is working correctly.
 
Associated Alerts: TCR-4897 - 11/17/2025 - COLIFORM (TCR)

TCR-4898 - 11/17/2025 - COLIFORM (TCR)

TCR-4872 - 11/12/2025 - COLIFORM (TCR)



More information for this water system: SDWIS ID 1745
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
PFAS data are now located on the Chemical Results page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Main menu:
Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login