OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00744 | ||
PWS Name: | KEIZER, CITY OF | ||
Who Was Contacted: | SDWIS | ||
Contact Phone: | 971-673-0417 (Email address hidden) | ||
Contact Date: | 04/12/2019 | ||
Contacted By: | SKERBECK, TIA (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | VOCs |
||
Details: | Toluene: A sample from EP-E Entry Point for Cherry Avenue was collected 3/14/19 had low detects of Toluene. ACTION NEEDED: Toluene: Confirmation sample from same sample site within this quarter, and begin quarterly monitoring of Toluene at EP-E. Trichloroethylene: A sample from EP-K Willamette Manor well collected 3/14/19 had low detects of TCE. This well is already on an annual testing schedule for this contaminant. The TCE level is about 1/14 of the MCL at this time. ACTION NEEDED: Trichloroethylene: No further action needed at this time. This well is required to be tested for these contaminants annually during the 1st quarter of the year (Jan-March) starting 2010: next tests due 1st quarter of 2019. Annual testing is required as long as detections occur. Tetrachloroethylene: A sample from EP-K Willamette Manor well collected 3/14/19 had low detects of PCE and TCE. This well is already on an annual testing schedule for these contaminants. The PCE level is just above the detection limit and about 1/7 of the MCL at this time. The TCE level is about 1/3 of the MCL at this time. ACTION NEEDED: No further action needed at this time. This well is required to be tested for these contaminants annually during the 1st quarter of the year (Jan-March) starting 2010: next tests due 1st quarter of 2019. Annual testing is required as long as detections occur. Note: the water system voluntary samples more frequently than is required. Note: the water system voluntary samples more frequently than is required. |
||
Associated Alerts: | CHEM8294 - 04/11/2019 - TETRACHLOROETHYLENE , TOLUENE , TRICHLOROETHYLENE |