OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00744 | ||
PWS Name: | KEIZER, CITY OF | ||
Who Was Contacted: | SDWIS | ||
Contact Phone: | 971-673-0425 (Email address hidden) | ||
Contact Date: | 10/24/2019 | ||
Contacted By: | BYRD, MICHELLE (DWP) | ||
Contact Method/Location: | Phone | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | VOCs |
||
Details: | Samples collected at the Willamette Manor entry point (EP-K) on August 21, 2019 detected trichloroethylene at 0.0014 mg/L, and on September 12, 2019 at the same entry point detected tetrachloroethylene at 0.0007 mg/L and trichloroethyene at 0.0014 mg/L. All detects were below the MCL of 0.005 mg/L. For years, the city has monitored these chemicals. Although sampling each chemical is required yearly, the city voluntarily samples monthly to monitor chemical trends. | ||
Associated Alerts: | CHEM8635 - 10/23/2019 - TETRACHLOROETHYLENE , TRICHLOROETHYLENE |