OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00789
PWS Name: SANDY, CITY OF
 
Who Was Contacted: Mike Walker
Contact Phone: 503-668-5533 (Email address hidden)
Contact Date: 12/13/2019
Contacted By: NUSRALA, JAMES (DWP)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Operations
 
Details: City detected HAA5 at over the MCL level of 0.060 mg/L during 4th quarter at 14665 Bluff Rd, compliance point, as well as at 37801 Cascadia Villa, an non-compliance DBP site. This is not an MCL violation as the running annual averages are below the MCLs for both TTHM and HAA5. Mike indicated fall brings higher DBP levels. As a result, City will take one of the storage tanks out of service to reduce water age in distribution. If this does not work, City will clean the tank from Portland's connection to try and reduce organic loading from this source. As a result of LRAAs over half the MCLs for HAA5, City will need to revert back to routine DBP schedule of 4 sites per quarter, beginning with 1st quarter 2020. Mike to provide two additional DBP sites to DWS to assign as sampling locations.
1/21/20 update: City will increase from 2 to 4 sites per quarter beginning in 1st quarter 2020 (March). City will sample at 37801 Cascadia Villa, a standard monitoring site from the IDSE with HAA5 values over the MCL, and 16610 Champion Way, a stage 1 DBP site with HAA5 levels also over the MCL, in addition to Pioneer and Bluff sites. By the way, since City population has recently grown to over 10,000 people, need to sample at 4 DBP sites a quarter, regardless.
 
Associated Alerts: CHEM8737 - 12/12/2019 - TOTAL HALOACETIC ACIDS (HAA5)



More information for this water system: SDWIS ID 3907
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login