OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00318
PWS Name: GEARHART WATER DEPARTMENT
 
Who Was Contacted and Phone: Dennis McNally (503) 738-5501
Contact Date: 11/20/2008
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
DBPs
 
Details: SUMMARY: TTHM and HAA5 single result exceeded MCL DETAILS: Sampling completed 10/15/08 indicated a TTHM level of 0.0913 mg/l (TTHM MCL = 0.080 mg/l) and an HAA5 level of 0.0681 mg/l (HAA5 MCL = 0.060 mg/l). An MCL violation for DBPs is based upon a running annual averge (RAA) of quarterly samples. The RAA for all 4 quarters in 2008 is TTHM = 0.05777 mg/l and HAA5 = 0.0388 mg/l. The RAA for 2008 is less than that required for and MCL violation and disinfection benchmark profiling and since Gearhart purchases water from Warrenton who installed treatment for DBPs in roughly 2006, no further action is required at this time. Warrentons results for 4th quarter 2008 were below the TTHM and HAA5 MCL. ACTION NEEDED: No further action is required at this time.
 
Associated Alerts: CHEM3242 - 11/18/2008 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM

CHEM3242 - 11/18/2008 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM



More information for this water system: SDWIS ID 4038
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login