OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05581
PWS Name: WEISS ESTATES WATER SYSTEM
 
Who Was Contacted: Mike Murphy, Megan Maloney, Corinne Clifton
Contact Phone: -- (Email address hidden)
Contact Date: 07/05/2018
Contacted By: PARRY, BETSY (DWP)
Contact Method/Location: Email
 
Assistance Type: VIOLATION RESPONSE
Reasons: SWTR
 
Details: In June, the chlorine levels on the treatment report were again insufficient to meet CT or even the 0.2 mg/L minimum level at the EP for several days. Their DRC Mike Murphy and I exchanged emails, along with HOA president Corinne Clifton and secretary Megan Maloney. Mike said they found that the digital chlorimeter was not reading correctly and calibrating it did not help - it had to be reset to factory defaults by Hach. After that, the digital meter and the color wheel began tracking pretty closely. Weiss will receive two more 10-pt violations for June. I advised them that if the problems continue into August (5th month) our enforcement staff will get involved. As for public notice, the ongoing boil notice (last issued 6/2/18) should cover those requirements for the June violations as well. Meanwhile, the PH was elevated for 4 days in June (9-10). The pH meter checked out, so they had an equipment person look at it. Mike wonders if their CIP caustic soda is getting into the finished water. They also submitted a turbidity value of 1.29 for one day in June. The DRC believes that was a sampling error, but even so, it would not trigger a TT violation (must exceed 1 (1.49) NTU over 95 percent of readings).
 
Associated Violations: Viol #, - : -

Viol #, - : -



More information for this water system: SDWIS ID 3923
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login