PWS ID: OR41 00744
PWS Name: KEIZER, CITY OF
 
Who Was Contacted and Phone: sdwis
Contact Date: 02/15/2011
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
Nitrate
 
Details: SUMMARY: PCE and TCE detects, Nitrate detects DETAILS: A sample from EP-K Willamette Manor well collected 1/25/11 had low detects of PCE and TCE. This well is already on an annual testing schedule for these contaminants. Detections continue to be very low--just above the detection limit and about an order of magnitude below the MCL this time. Samples collected from EP-L 13th Ave well and EP-M 17th Ave well on 1/25/11 had detections of nitrate above half of the MCL-- these wells have historically had nitrate at these levels. ACTION NEEDED: No further action needed at this time. Willamette Manor is required to be tested for these contaminants annually during the 1st quarter of the year (Jan-March) starting 2010: next test due 2012.
 
Associated Alerts: CHEM4760 - 02/15/2011 - NITRATE , TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM4760 - 02/15/2011 - NITRATE , TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM4760 - 02/15/2011 - NITRATE , TETRACHLOROETHYLENE , TRICHLOROETHYLENE