OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00250
PWS Name: MILO ACADEMY
 
Who Was Contacted: Jeff Miller
Contact Phone: -- (Email address hidden)
Contact Date: 10/07/2020
Contacted By: TEMPLIN, REBECCA (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: Contacted Jeff with Milo Academy about the recent high result for HAA5, a disinfection by-product. The quarterly results were 0.0689 mg/L for the 3Q results. The LRAA is 0.044 mg/L which is below the MCL, so no increase in monitoring is required at this time. Jeff thinks there are 2 reasons for the high HAA5 result: 1) the water usage is down in the system, and 2) they recently changed sources which requires a higher chlorine dosage. In reviewing the data, Jeff plans to reduce the chlorine dosage because of the current temperatures and will also do more frequent flushing.
 
Associated Alerts: CHEM9088 - 10/06/2020 - TOTAL HALOACETIC ACIDS (HAA5)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3946