PWS ID: OR41 01139
PWS Name: MIDLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Darrel Lockard (503) 410-2173
Contact Date: 03/21/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
N/A
 
Details: SUMMARY: follow up on Boil Water Notice DETAILS: I have received some updated information from Darrel today, regarding the reasons for the high turbidity that conflict with earlier information received from Scott MacGregor. Darrel indicated that the spike of greater than 5 NTU was due to the streaming current meter (SCM) failing on the external setting. The SCM reading was not accurately representing the raw turbidity in its readings, and there was very little polymer being dosed. Also, Darrel indicated that both the on-line and bench top turbidimeters had not been calibrated recently and is concerned that they are not reading accurately-the readings are all over the board. Also, concerned that combined filter effluent meter is grabbing out of the clearwell and not directly off filters and could not be accurately measuring filter performance ACTION NEEDED: System to stay on boil notice until turbidity readings are accurate and meters are calibrated, and DWP has confidence that NTUs are under control. DWP to further investigate turbidity readings with operators and during 3/24 field inspection.


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login