OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01139
PWS Name: MIDLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Jim Kuhns (503) 308-3667
Contact Date: 03/22/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
N/A
 
Details: SUMMARY: Follow up actions - boil notice DETAILS: Jim summarized actions taken on 3/22. First he resoldered the instrument connections to the on-line 1720-C NTU meter, so that the effluent turbidity readings stabilized. He calibrated meter with non-expired Formazin. Both on-line and bench were comparable, but still reading between 1 and 1.5 NTU, higher than the raw water NTU. He then noticed that the polymer introduced a couple of days ago was feeding too much chemical, and the Streaming Current Meter (SCM) was registering a very high charge. He began using Midlands original polymer, and set feed pump on manual, feeding less chemical. SCM then read more of a neutral charge, and the effluent NTUs went down to 0.1. Chlorine residuals at plant are up to 1.4 mg/L. Jim felt root problem of high NTU and low residual chlorine was polymer pump is defective, and the high NTU was causing a high chlorine demand. ACTION NEEDED: Jim to purchase new polymer feed pump. Midland to flush high chlorine water through system, and take chlorine residual readings at far ends of distribution on Wed 3/23. DWP to ground truth effluent turbidity with bench top meter at site visit on 3/24, to verify NTUs are accurate. Midland will discuss with DWP taking coliform samples after residual restored, and NTUs to acceptable level to consider lifting boil water notice.


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login