OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00744
PWS Name: KEIZER, CITY OF
 
Who Was Contacted and Phone: sdwis
Contact Date: 06/13/2012
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: TCE detect DETAILS: Sample from EP-K Willamette Manor well collected 5/17/12 had low detect of TCE. This well is already on an annual testing schedule for this contaminant. Detections continue to be very low--just above the detection limit and about an order of magnitude below the MCL at this time. ACTION NEEDED: No further action needed at this time. This well is required to be tested for these contaminants annually during the 1st quarter of the year (Jan-March) starting 2010: next test due 2013.
 
Associated Alerts: CHEM5386 - 06/13/2012 - TRICHLOROETHYLENE