OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00744
PWS Name: KEIZER, CITY OF
 
Who Was Contacted and Phone: Pat Taylor (503) 856-3560
Contact Date: 07/16/2013
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
N/A
 
Details: SUMMARY: Diquat detection DETAILS: There was a slight detection of diquat during routine SOC monitoring 5/22/13 at EP-Q Keizer Station well. The lab detection limit for diquat is 0.0004 mg/L and the test result was 0.0007 mg/L. The results are well below the MCL for diquat of 0.02 mg/L. ACTION NEEDED: The system must conduct quarterly monitoring for diquat at this well for at least 2 more quarters beginning 7/1/13 (monitoring must occur July-Sept and Oct-Dec 2013). Review after 2 quarters and if results still below MCL, monitoring will be changed to annually during the 2nd quarter for 3 years beginning 1/1/14.
 
Associated Alerts: CHEM5845 - 07/16/2013 - DIQUAT