OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00744
PWS Name: KEIZER, CITY OF
 
Who Was Contacted and Phone: sdwis
Contact Date: 12/22/2015
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: TCE detect DETAILS: A sample collected from EP-K Willamette Manor well on 11/18/15 had a low detect of TCE. This well is already on an annual testing schedule for this contaminant. The TCE level was above the detection limit and about 1/4 of the MCL at this time. ACTION NEEDED: No further action needed at this time. This well is required to be tested for this contaminant annually during the 1st quarter of the year (Jan-March) starting 2010: next test due 1st quarter of 2016. Annual testing is required as long as detections occur. Note: the water system voluntary samples more frequently than is required.
 
Associated Alerts: CHEM6995 - 12/22/2015 - TRICHLOROETHYLENE