OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00953
PWS Name: WILLAMINA, CITY OF
 
Who Was Contacted and Phone: Matt Griffith (503) 437-7003
Contact Date: 06/19/2007
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Chlorine
SWTR
 
Details: SUMMARY: Low chlorine residual #4 DETAILS: continued from #3...On Monday evening, Matt decided not to dose the tanks with extra chlorine as I requested. He figured flushing the tank out would move the water through there fast enough, since he had already jacked up the chlorinator. I told him he still should have dosed it. The residual at the first user was up to 0.5 ppm by 10 pm. On Tuesday morning residuals in town were at least 0.4 ppm. They flushed water out of the tank to get out the low chlorine water, and also flushed in the middle of town, to bring in the higher chlorinated water. No flushing was done further out than that. only one residual reading was taken at the end of a line, and this was at the wastewater plant, a dead end line. The residual there was 0.05 ppm.

We also looked at CTs. With 168 minutes of contact time (just through 1 tank, the report for the time through both tanks is not complete but they likely have roughly 25% more), and a minimum chlorine residual of 0.1 ppm, that gives a CT of 17. The temperature was 16 degrees, ph = 7.6, the CT required = 14. So CT requirement was met. He had not yet calculated the CTs yet though, so he is not doing them every day. The weekend operators (unless it’s Matt’s turn) do not figure CTs. Matt is trying to convince the superintendent that is important, but currently they have an interim superintendent who is not certified. ACTION NEEDED: Develop detailed protocol for operators, O&M manual, review contract with DRC. Communications meeting on Friday to discuss ways to improve. They will soon hire a water superintendent who will hopefully be certified at the appropriate level. They are also working on a new chlorination room with all the alarms and recorders.


More information for this water system: SDWIS ID 4690
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login