OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00805
PWS Name: MAPLE ELSIE WATER SERVICE
 
Who Was Contacted and Phone: Bob Jones (503) 717-2726
Contact Date: 09/26/2008
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: E. coli positive DETAILS: Bob called to report that the September 25th sample collected at the end of the line tested positive for both total coliform and e.coli. Results came back from the lab at 10:30 am on Sept. 26th. Sampling was conducted in the normal routine manner. Mentioned to Bob that Evergreen Acres needed to take four total coliform repeats within 24 hours, and if any of these repeats come up positive, a tier 1 public notice (boil water notice) will need to be made. Mentioned to Bob that he should shock chlorinate the well after the repeats. Told Bob that they will need to take five total coliform routines during the month of October. Faxed the directions for shock chlorinating the well and the tier 1 public notice template to Bob. ACTION NEEDED: Bob will take the four repeats at the appropriate locations for total coliform within 24 hours. Bob will file a Tier 1 public notice if any of the repeats come up positive. Bob to contact DWP if any of the repeats are positive. DWP to provide support if necessary, especially if any of the repeats come up positive.
 
Associated Alerts: COLI5664 - 09/26/2008 - COLIFORM (TCR) , E. COLI

COLI5664 - 09/26/2008 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3789
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login