OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00002
PWS Name: ADRIAN, CITY OF
 
Who Was Contacted and Phone: Dick Davis, DRC (541) 372-2611
Contact Date: 01/23/2009
Contacted By: BURNETT, GARY (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: Repeat samples TC positive, TCR MCL violation for January DETAILS: 3 Repeat samples taken 1/20/2009 were total coliform positive. The original Routine taken on 1/06 was total coliform positive so it is an MCL violation for January. A sample taken at the primary supply well was coliform negative. Chlorine residuals (free) in the system were reported at about 0.2 mg/l using a digital test kit. Dick will check the calibration of the test kit by consulting with City of Nyssa staff.The week of January 26 he will try batch chlorinating in the reservoir with Miox from the City of Ontario and then take more coliform samples prior to February. The City has discontinued the poyphosphate treatment at this time due to equipment problems. ACTION NEEDED: City to send out public notification for total coliform MCL violation. Five Routine samples required in February.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3682