OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05581
PWS Name: WEISS ESTATES WATER SYSTEM
 
Who Was Contacted and Phone: Jerry Bolden (541) 347-3549
Contact Date: 04/03/2009
Contacted By: MACPHERSON, JAMES (REGION 2)
Contact Method/Location: Field
 
Assistance Type: OTHER REGULATORY - WATER TREATMENT PLANT EVALUATION*
Reasons: Operations
SWTR
 
Details: SUMMARY: Water Treatment Plant Inspection DETAILS: Finished water treatment plant inspection started on previous visit. Noted that turbidity meter inlet needs to be plumbed immediately after filter housings where flow combines to one pipe. Recommended plumbing change to include moving hypochlorite addition from dead end into main pipe. If that does not increase chlorine residual in distribution system, suggested increasing dosage of hypochlorite. Obtain filters with lower nominal pore size. Use HBH circuit rider to conduct tracer study. Get analysis of ozone concentration in effluent from last storage tank. ACTION NEEDED: Replumb turbidity tap, pre-hypochlorite tap, test for change. Have tracer study conducted. Measure ozone concentration.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3923