Details: SUMMARY: Follow up on SWTR compliance DETAILS: Jim and I discussed SWTR compliance at Midland. We reviewed HBHs recent site visit report and discussed calculating contact times, based on observed peak hourly demand flows every day, to reflect worst case conditions for that day, rather than using the summertime absolute highest flow year round. Midland will appropriately convert total 24-hour flows to peak hourly accounting for the excessive leakage. Discussed methodology for determining peak hourly demand flows with Jim. Jim also indicated that the 42,000 gallon storage tank will be kept at a minimum storage volume of half full. Also I provided Jim with template public notices for exceeding monthly NTU limit (< 0.3 95 % of time) in Dec and not meeting CTs in Dec and Jan. ACTION NEEDED: Jim to write peak hourly demand flow every day on monthly SWTR form from here on out, and notify DWP right away if tank volume drops below half full, or CTs not being met, or turbidity spikes above 0.3 NTU. DWP to continue to support Midland as Jim is operating plant during period until they find a certified operator.


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login