OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01139
PWS Name: MIDLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Jim Kuhns (503) 308-3667
Contact Date: 03/24/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
N/A
 
Details: SUMMARY: Treatment plant visit to address boil water notice DETAILS: DWP conducted treatment plant inspection with Jim, and City of Rainier and OAWU, in response to reported NTU > 1.49 and chlorine residual at 0.03 mg/L on 3/18/11. Inspected chart recorders on 3/18, and in early am NTUs spiked up to only 0.95 NTU. Verfified low residual of 0.03 mg/L. The plant never spiked to 5 NTU on 3/18 as reported to DWP earlier. On 3/21 chart, turbidities spiked up to 1.4 NTU, as Jim was working to reconnect wires to instrument. Both on-line and benchtop calibrated to acceptable standards at Midland. Polymer dosages adjusted to bring NTUs down on 3/21. Residual restored to > 1 mg/L quickly after 3/18 low level, as verified on the charts. It was determined that even though NTUs never exceeded 1.49, that given such low residuals (almost no disinfection on 3/18-CTs not met), and questionable turbidities, that two routine bacti samples in system are needed before boil to be lifted. ACTION NEEDED: Jim to take 2 routine bactis on 3/25 in the am and take to lab. Results due on 3/25 or 3/26. Jim to have results sent to DWP on either Fri or Sat. to discuss lifting boil notice. Jim to replace polymer feed pump with more reliable version that communicates well with Streaming Current Meter.


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login