OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00744
PWS Name: KEIZER, CITY OF
 
Who Was Contacted and Phone: Pat Taylor (503) 856-3560
Contact Date: 05/23/2014
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine positive total coliform DETAILS: Pat reported that a routine sample collected from 2275 Manzanita on Monday 5/19 was positive for total coliform. Three repeats samples were collected on Tuesday 5/20 (upstream, downstream, and original site), as well as six triggered source water samples from the wells that were running at the time (Willamette Manor, Keizer Station, Delta, Carlhaven West, Carlhaven East, & Lacey Ct.) Pat didnt have a theory on a possible cause for the positive (no unusual activity occurring). He noted that this same site had a positive about this same time of year, a year ago. ACTION NEEDED: Results from all repeats and triggered source water samples were absent for coliform. No further action needed at this time.
 
Associated Alerts: COLI12840 - 05/21/2014 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3787
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login