OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05581
PWS Name: WEISS ESTATES WATER SYSTEM
 
Who Was Contacted and Phone: Jim Lea
Contact Date: 11/05/2014
Contacted By: MACPHERSON, JAMES (REGION 2)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
Chlorine
 
Details: SUMMARY: Boil Water Advisory - loss of chlorine residual DETAILS: The overnight theft of water has stopped. Thus, the residence time of treated water in the "clearwell" (5 2,500 gallon tanks in series) increased markedly. The result is that the chlorine residual at the outlet of the clearwell went to undetectable. Thus, a boil water advisory will be issued. The corrective action will be to increase the inlet dose of hypochlorite, likely to about 3 mg/L. Then monitor the outlet chlorine residual until it exceeds 0.3 mg/L at which point CT will be met. ACTION NEEDED: Tracer study needed. The assumed contact time of 120 minutes is a conservative estimate. A tracer study will allow for a likely longer contact time and a resultant reduction in required chlorine residual.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3923