OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01139
PWS Name: MIDLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Phil White (360) 560-0248
Contact Date: 08/31/2015
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Operations
 
Details: SUMMARY: Follow up to turbidity spike 8/29/15 DETAILS: Phil called at 9:30 am to inform me that filtered turbidity spiked up to 1.78 NTU for a brief (30-60 min.) period between 6:30 am and 8 am on 8/29, due to high (6.5 NTU) Graham Creek water and high demand (PASS-CX feed and filter could not keep up with amount of turbid water sent through plant). Phil responded to the high NTU alarm and by 730 am on 8/29 was manually setting the streaming current detector to feed more PASS-CX and backwashed the filter. By 8 am, filtered NTU down to around 0.16. Given that approximately 5700 gal of high turbid water (95 gpm plant flow for 60 min.) would have likely been flushed due to 80-90,000 gal/day usage over past 2 days, 4-hour reads < 1.49 NTU, and chlorine residuals high enough to meet CTs easily, I decided not to require a boil water notice now. I reminded Phil to contact DWS right away in future for any NTU spike. Phil has DWS after hours #. ACTION NEEDED: Midland to collect September coliform sample(s) this Wed and note on August monthly report if filtered turbidity triggers exceeded (yes/no). Midland to continue to address high NTU spikes by fixing leaks in distribution system to slow plant down and allow flexibility to wait out high storms by using storage in future. Creek intake and raw sedimentation will be getting cleaned out. System will continue to try to address streaming meters ability to handle power outages and raw NTU spikes to feed appropriate chemical for flocculation. 10/22/15 update: IFE trigger exceeded for August (2 consecutive 15 min. readings > 1.0 NTU). System has met requirements by stating reason for exceedence on SWTR form. I requested a filter turbidity backwash profile from operator. 11/16/15: System produced filter NTU profile from 11/15/15. Only optimization goal not met was system returned to service at > 0.10 NTU (0.13 NTU).


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login