OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00601
PWS Name: HILAND WC - RIVERBEND
 
Who Was Contacted and Phone: Silas Olson (503) 554-8333
Contact Date: 10/11/2015
Contacted By: TEAMUS, JOSHUA (LINCOLN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine Sample 10/11/2015 - Total Coliform Positive DETAILS: I spoke with Mariland at Highland, who spoke with Silas. He said Highland has already sent out someone to do a repeat samples, since repeat samples are required within 24 hours of the positive notification. Their Operation and Maintenance Manual outlines their procedure for responding to a routine sample coming back positive for total coliform, and they appear to be following it. The routine was taken at site #2. The manual proscribes the four repeats as 45 Modlin Ln, 58 Modlin Ln, 745 North Bank Rd, and Source. Since the system is ground water with no treatment, the fourth repeat will be labeled as triggered and be taken from the source. ACTION NEEDED: If any of the repeats come back positive for total coliform the system should issue their total coliform letter to the systems users.In addition, Highland is required to collect five routine samples the following month regardless of the results of the repeat samples. This is also outlined in their manual.
 
Associated Alerts: COLI14825 - 10/13/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3376
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login