OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 92104
PWS Name: DIAMOND LAKE LODGE/RESORT
 
Who Was Contacted and Phone: Larry McCall (541) 430-3978
Contact Date: 04/18/2016
Contacted By: GROSS-REGAN, CAROLINE (DOUGLAS COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Lead or Copper
 
Details: SUMMARY: Meeting to Discuss Follow-up to Positive Repeat Total Coliform Protocols and Water Quality Parameter Testing Regarding >MCL for Lead DETAILS: System operator needs to do Level One Investigation (provided form) for exceding MCL on TC, and resolve the problem. Because system samples coliform monthly - no more (temp routine) coliform samples needed in May - just take the monthly coliform in distribution. Operator needs to read materials provided on controlling lead and copper take the Ph, Alkalinity, Calcium, Conductivity and temperature etc, at two sites in distribution and at the entry point. Another round of same to follow - two weeks after initial round. Also a lead and copper of the source water. ACTION NEEDED: Take above WQPs -important to take the pH as soon as water is drawn, as well as record the temperature. Lead and copper to be taken in two rounds this year (5 samples each). Once before June 30 and once again before Dec 31.
 
Associated Alerts: COLI15418 - 04/15/2016 - COLIFORM (TCR)

COLI15418 - 04/15/2016 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3675
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login