Date
#
Samples
Sample
Type
Coliform
Type
Result Sample
ID
Repeat of
Sample ID
Sample
Site
Facility Chlorine
Residual
Received
Date
Rejected
Reason
Jun 12, 2024 1RT Total Absent 20240863 BATHROOM SINK DIST-A 2.80Jun 13, 2024
Apr 17, 2024 1RT Total Absent 20240581 BATHROOM SINK DIST-A 2.20Apr 18, 2024
Dec 12, 2023 1RT Total Absent 20231877 BATHROOM SINK DIST-A 2.50Dec 13, 2023
Sep 12, 2023 1RT Total Absent 20231334 BATHROOM SINK DIST-A 2.80Sep 13, 2023
Jun 13, 2023 1RT Total Absent 20230778 BATHROOM SINK DIST-A 2.20Jun 14, 2023
Apr 04, 2023 1RT Total Absent 20230450 BATHROOM SINK DIST-A 3.00Apr 05, 2023
Dec 20, 2022 1CO Total Absent 20222033 20221982 SPRING SRC-AA Dec 21, 2022
Dec 20, 2022 1CO Total Absent 20222032 20221982 SPRING SRC-AA Dec 21, 2022
Dec 20, 2022 1CO Total Absent 20222031 20221982 SPRING SRC-AA Dec 21, 2022
Dec 20, 2022 1CO Total Absent 20222030 20221982 SPRING SRC-AA Dec 21, 2022
Dec 20, 2022 1CO Total Absent 20222029 20221982 SPRING SRC-AA Dec 21, 2022
Dec 13, 2022 1AS Total POSITIVE 20221982 SPRING SRC-AA Dec 14, 2022
AS E. coli POSITIVE 20221982 SPRING SRC-AA
Dec 13, 2022 1RT Total Absent 20221981 BATHROOM SINK DIST-A 3.60Dec 14, 2022
Sep 26, 2022 1RT Total Absent 20221552 BATHROOM SINK DIST-A 1.60Sep 27, 2022
Jun 06, 2022 1RT Total Absent 20220914 SINK DIST-A 1.30Jun 07, 2022
Mar 01, 2022 1RT Total Absent 20220363 SINK DIST-A 1.80Mar 02, 2022
Dec 07, 2021 1RT Total Absent 20212049 SINK DIST-A 1.20Dec 08, 2021
Sep 14, 2021 1RT Total Absent 20211505 SINK DIST-A 1.40Sep 17, 2021
Jun 02, 2021 1RT Total Absent 20210846 SINK DIST-A 2.80Jun 04, 2021
Sample
Date
#
Samples
Sample
Type
Coliform
Type
Result Sample
ID
Repeat of
Sample ID
Sample
Site
Facility Chlorine
Residual
Received
Date
Rejected
Reason
May 18, 2021 1RT Total Absent 20210772 SINK DIST-A 2.40May 20, 2021
May 18, 2021 1RT Total Absent 20210771 SINK DIST-A 2.20May 20, 2021
May 11, 2021 1RT Total Absent 20210712 SINK DIST-A 3.40May 12, 2021
Feb 08, 2021 1TG Total POSITIVE 20210186 20210155 SPRING SRC-AA Feb 09, 2021
TG E. coli POSITIVE 20210186 20210155 SPRING SRC-AA
Feb 08, 2021 1RP Total Absent 20210189 20210155 SINK DIST-A 2.60Feb 09, 2021
Feb 08, 2021 1RP Total Absent 20210188 20210155 SINK DIST-A 2.60Feb 09, 2021
Feb 08, 2021 1RP Total Absent 20210187 20210155 SINK DIST-A 2.60Feb 09, 2021
Feb 02, 2021 1RT Total POSITIVE 20210155 98412 CARLA LN SINK DIST-A 0.20Feb 05, 2021
RT E. coli Absent 20210155 98412 CARLA LN SINK DIST-A 0.20
Jan 06, 2021 1AS Total POSITIVE 20210036 SPRING SRC-AA Jan 08, 2021
AS E. coli POSITIVE 20210036 SPRING SRC-AA



See also:  Coliform Fact Sheet  ::  Coliform Schedules  ::  Archived Results  ::  Batch Numbers

Sample types:  AS=Assessment, CO=Confirmation, MU=Make-up, RP=Repeat, RT=Routine, SP=Special, TG=Triggered. See the glossary for more information.

Filter options:  Show special samples  ::  Hide rejected samples  ::  Include results older than 2021



More information for this water system: SDWIS ID 2883
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login